REMKOManual for experienced specialistsHEAT PUMP MANAGERMULTI-TALENT PLUSWITH HEAT FLOW VOLUMEMETEREdition GB – W05
REMKO Heat Pump ManagerLevel 4PlantEnd01Operating modeLanguageLCD contrastLCD brightness°C/°FHot waterEnd011 x hot waterT-WW 1 targetT-WW 2 targetT-WW
Level 4 - continued0-10V I/OEnd01SPG curveCurve 11 U 1Curve 11 U 2Curve 11 T 1Curve 11 T 2Curve 11 U AScreedEnd01ScreedScreed programmeHot waterEnd01C
REMKO Heat Pump ManagerLevel 4 - DISPLAY - Description of parameters and settingsDISPLAYHot waterEnd01T-WWT-WW UWW demandWW pumpWW enableCirculation p
Hot waterDesignation DescriptionT-WWCurrent hot water temperature and hot water target temperature (see user hot water T-WW target). [sensor 06]T-
REMKO Heat Pump ManagerPlantDesignation Value range Factory setting DescriptionOperating mode / Operating modeStandby CoolingAutomatic 1+2 SummerHeati
Hot waterDesignation Value range Factory setting Description1xhot water On/Off OffThe tank is only enabled for a one time loading (= ON) (e.g. for sh
REMKO Heat Pump ManagerHeating circuit 1/2-continuedDesignation Value range Factory setting DescriptionT-absent 5.0°C-40.0°C 15.0°CSetting the desired
Heating circuit 1/2-continuedDesignation Value range Factory setting DescriptionT-supply const T 10°C-110°C 35.0°CThe T-supply const function must be
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionMax warm up-time 00:00-03:00 02:00Setting the time by which the heating star
Factory settingDesignationDay TimeOperating mode / descriptionHeating circuit 1 prog 1Mo.-Fr. Mo.-Su.Sa.+Su. 06:00-22:0006:00-22:0007:00-23:00Automati
REMKO Heat Pump ManagerVarious values are summarised here for the user to provide quick access.Designation Factory setting DescriptionTimeThe controll
Various values are summarised here in order toe enable quick access for customer service.The input of the code number is necessary for some functions.
REMKO Heat Pump ManagerDesignation DescriptionSoftware number Display of the software number with index.Manual cascade operationOnly for cascades; the
SPECIALISTCongurationEnd01Terminal addressBUS code 1BUS code 2eBUS supplySystem selectionRegulator typeWE 1 typeWE BUSWE 2 typeWE 2 tankWE 3 typeWE 4
REMKO Heat Pump ManagerConfigurationDesignation Value range Factory setting DescriptionTerminal address On/Off OnThe BM-T is a terminal (input device).
Configuration - continuedDesignation Value range Factory setting DescriptioneBUS supply On/Off OffActivating the eBUS supply in accordance with the con
REMKO Heat Pump ManagerConfiguration - continuedDesignation Value range Factory setting DescriptionWE BUS 00-05 05•00 = Relay (switching WE).•01 = CA
Designation Value range Factory setting DescriptionWE 2 tank (continued)00-03 00Switching characteristics:The pump switches on if the temperature of t
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionCooling mode On/Off On Enabling the operating mode cooling and the required
Heating applianceDesignation Value range Factory setting DescriptionMax T-collector 30.0°C-110.0°C 70.0°C Setting the maximum collector temperature [s
Contents Read these operating instructions carefully before commissioning / using this device! These instructions are an integral part of the syste
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionHyst burner 2 2.0K-20.0K 2.0KOnly for two stage burners or solid material in
CascadeDesignation Value range Factory setting DescriptionWE found 1-3---/x-x--- 1-3/x-xDisplay of the heating appliance automatically logged by the
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionWE Dyn up 20-500 350Setting the value for the connection of all WE-levels (W
Heat pumpDesignation Value range Factory setting DescriptionMax T-return WP 30.0°C-110.0°C 60.0°CSetting the system's maximum return temperature
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionE 1 function 00-03 02Description see specialist configuration.E 2 function
0-10V I/ODesignation Value range Factory setting DescriptionSPG curve 00-11 11 Selection for the voltage curves for the configuration of the voltage in
REMKO Heat Pump ManagerHot waterDesignation Value range Factory setting DescriptionCharge pump lock On/Off OffActivating the 3-way switch valve for pr
Designation Value range Factory setting DescriptionHysteresis WW 3. 0 K - 3 0. 0 K 5. 0 KSetting the hot water hysteresis.Water heating starts if the
REMKO Heat Pump ManagerHeating circuit 1/2Designation Value range Factory setting DescriptionHC functionStandardT-supply constSwimming pool (HC2)WW(HC
Designation Value range Factory setting DescriptionOperation HCPStandardHeating limitsonly time progContinuous operationStandardSetting the operating
REMKO Heat Pump ManagerSafety notesWarrantyA prerequisite for any warranty claims is that the enclosed "war-ranty registration card" was com
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionMin T-supply 10.0°C-110.0°C 18.0°CSetting the minimum supply temperature for
Solar / MFDesignation Value range Factory setting DescriptionMF 1 function(Output A8 enable 2nd heating appliance)00-37 37Function selection for the M
REMKO Heat Pump ManagerSolar/MF - M 4 function - continuedLevel 4 - SPECIALIST - Description of parameters and settings - continuedDescriptions of add
Solar/MF - M 4 function - continuedLevel 4 - SPECIALIST - Description of parameters and settings - continuedDescription•24 = return riser WE 1.T-retu
REMKO Heat Pump ManagerDesignation Value range Factory setting DescriptionMF 4 Hyst 2.0K-10.0K 5.0K Setting the MF 4 hysteresis.MF 4 Hyst Off 2.0K-10.
Designation Value range Factory setting DescriptionRe-cooling differ-ence0.0K-30.0K 20.0KSetting the return cooling difference.If the collector protec
REMKO Heat Pump ManagerSystem selection12 basic hydraulic configurations are provided in the heat pump manager which can be pulled up with the system s
F9F6F8ABABVVF17F11II0IA9A8A3A6A121)A1M2)1)F5A2A4/A5Designation Value range ProgrammingBUS code BM Off, 00-15 OffLanguage D/GB/F/NL/E/I D (German)Termi
REMKO Heat Pump ManagerF9F8ABABVVF17F11II0Il/hTmaxF6A9A8A3A6A12A101)A1M1)F5A2A4/A52) 3)Designation Value range ProgrammingOutput/level 00 – 9950 kWWE
F6F17VVBAABF8II0IF11F9A12A61)A1M2)1)F5A2A4/A5Designation Value range ProgrammingOutput/level 00 – 9950 kWWE 1 level 1 = 50WE 3 level 1 = 1continue wit
FunctionIt is the function of the Multi-talent heat pump manager to operate and effectively manage the entire warm water pump system including any add
REMKO Heat Pump ManagerBAABF9F14ABABF6F8F12ABABl/hTmaxVVF17F11II0I3)A9A3A6A12A3A10A8M2)1)F5A2A4/A5A104)Designation Value range ProgrammingOutput/level
F14A12F6F17VVBAABF8II0IF11F9A12A61)A1M2)1)F5A2A4/A5F12Designation Value range ProgrammingOutput/level 00 – 9950 kWWE 1 level 1 = 50WE 3 level 1 = 1con
REMKO Heat Pump ManagerF9F8VVF17F11II0Il/hTmaxF6MA9A8A6A12A8A101)A1M1)F5A2A4/A52) 3)ABABA3Designation Value range ProgrammingOutput/level 00 – 9950 kW
F9F14ABABF6F8F12ABABl/hTmax.3)VVF17F11II0IA9A8A3A6A12A3M2)1)F5A2A4/A5Designation Value range ProgrammingOutput/level 00 – 9950 kWWE 1 level 1 = 50WE 3
REMKO Heat Pump ManagerF9F14ABABF6F8F12ABABl/hTmax.3)VVF17F11II0IMA9A8A3A6A12A3A8M2)1)F5A2A4/A5Designation Value range ProgrammingOutput/level 00 – 99
F9ABABF6F8F1ABABl/hTmaxF14VVF17TH2F11II0I3)A9A8A3A6A12A3M1)F5A2A4/A5Designation Value range ProgrammingOutput/level 00 – 9950 kWWE 1 level 1 = 50WE 3
REMKO Heat Pump ManagerContact layout Merlin I/O circuit board (solder side view)Please also note the connection diagrams or the electrical circuit di
Troubleshooting and customer serviceFault numbers appear in the controller display if your heating system malfunctions. There are three types of repor
REMKO Heat Pump ManagerFault Possible cause Checks Remedial measuresCommunications faultBus and sensor wiring were laid togetherCheck connection cable
Display Fault descriptionE 54Heat pump fault The flow monitor has tripped. A flow problem has occurred. Possible causes are air in the system, a clogged
REMKO Heat Pump ManagerHeating curves The heating curve is used for the purpose of assigning the building and appropriate target supply tem-perature i
REMKO Heat Pump ManagerTemperature 5 kOhm sensor (NTC) Pt1000 (solar/solid fuel)-60℃ 698961 Ohm --50℃ 333908 Ohm --40℃ 167835Ohm --30℃ 88340 Ohm --20℃
Notes
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!ConsultingThanks to intensive training, our c
Commissioning The commissioning and pro-gramming of the heat-pump manager may only be carried out by a mechanic authorised by REMKO. NOTE
REMKO Heat Pump ManagerFunctions heat flow metersDisplay levelThe displays relevant to the heat flow meters are called up with the following steps on th
Menu structure / menu navigationLevel 1 Level 2 Level 3Level 0T-externalT-collectorAutomatic 1MoHome08:3030 Mar 0915.3 °C 36.2 °C Main menuEnd01Ter