Edition GB – T10REMKO RVTRVT 261DC, RVT 351DC, RVT 521DC Inverter wall - room air conditioner in split designOperation · Technology · Spare parts
HEATING- MODEHeating mode operational sequence> 6 Min.> 3 Min.> 6 Min.30 sec. 30 sec.Nominal temperature +5 °CNominal temperature +2 °CFan op
The fan speed can be adjusted with this button. A selection can be made between low, medium, high and automatic fan speed.FAN ButtonFANIn ventilation
The activation and switch-off time can be programmed with this button. The timer is activated/deactivated by means of pressing the timer on and the ti
ShutdownTemporary shutdown1. Allow the indoor unit to run for 2 to 3 hours in air circulation mode or in cooling mode at the maximum temperature sett
Cleaning the condensation pump (optional equipment)An optional integrated or separate condensation pump may be included on the indoor unit, which pump
Troubleshooting and customer serviceThe equipment and components are manufactured using state-of-the-art production methods and tested several times t
Problem display by blinker codeDisplay Cause Required actionE1 Communication error between outdoor component and indoor unit Contact specialist firmE3
Selection of the installation locationIndoor unitThe indoor unit is designed for horizontal wall installation above doors. However, it can also be use
2001201500120120Installation inside buildings Ensure there is adequate heat dissipation when placing the outdoor component in cellars, attics, adjoin
Mounting points for wall bracket RVT 261DC ITRVT 351DC ITRVT 521DC ITAll dimensions in mm100050298656550750250656545815270656545Connection variati
The units are factory filled with dry nitrogen to check for leaks. The pressurised nitrogen is released when loosening the union nuts. CAUTIONCon
Supplementary information for installation When combining the outdoor component with some indoor units, the connection of the refrigerant pipes may d
Condensation connection - outdoor componentOpening for condensation connection Condensation pan of outdoor componentCondensation connectionAll electri
Check all plugged and clamped terminals to verify they are seated correctly and making a permanent contact. Re-tighten as required. CAUTION 12
TransformerElectrical circuit diagramRVT 261-351DC ITRVT 261-351DC ATMains cable 230V / 1~ /50 Hzto outdoor componentAir circulation sensorCRYY/GRWAut
34M~MRVT 521DC ITTransformerMains cable 230V / 1~ /50 Hzto outdoor componentSensor Air circulationCR YY/GSensor VaporiserDisplay DisplaySwing motorE
Add refrigerantThe equipment contains a basic quantity of refrigerant. Beyond these conditions, for refrigerant pipe lengths of more than 5 meters per
Final tasks Re-fit all the dismantled parts. Familiarize the operator with the system.Functional test for cooling and heating modes1. Remove the cap
Unit dimensions We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.RVT 261DC
Exploded view of RVT 261DC IT to RVT 521DC IT193781221011456We reserve the right to modify the dimensions and constructional design as part of the on
ContentsThis operating manual is a translation of the German original.These operating instructions should be read carefully prior to commissioning /
Exploded view RVT 261-521 DC / ATSpare parts listNo. Designation RVT 261DC AT RVT 351DC AT RVT 521DC AT1 Front panel1109761 1109778 11097952 Fan blad
Technical dataSeries RVT 261DC RVT 351DC RVT 521DCOperating mode Inverter-wall room air conditioner combination for cooling and heatingNominal cooling
Subject to technical modifications, no responsibility taken for the correctness of information!ConsultancyIntensive training means our consultants are
Safety notesDisposal of packagingAll products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing
The equipment is shipped in sturdy transport packaging. Immediately check the equipment on delivery and make a note of any damage or missing parts on
OperationInfrared remote controlThe infrared remote control sends the programmed settings over a distance of up to 6 m to the receiver of the indoor u
"FAN" button Press this button to set the required fan speed. 4 settings are available: automatic, high, medium and low fan speed. &quo
A symbol is shown on the display to indicate that the settings are being transferred.By pressing the ON / OFF button, you can activate or deactivate y
> 6 Min.> 3 Min.> 6 Min.30 sec. 30 sec.Nominal temperatureNominal temperature -2°CFan operation ITFan operation ATCompressor operation ATActu